780 CMR, 415.7

Current through Register 1529, August 30, 2024
Subsection 415.7 - Groups H-3 and H-4

Groups H-3 and H-4 shall be constructed in accordance with the applicable provisions of this code and the International Fire Code. [F]

415.7.1 Flammable and combustible liquids. The storage, handling, processing and transporting of flammable and combustible liquids in Group H-3 occupancies shall be in accordance with Section 415.6.2. [F]
415.7.2Gas rooms. When gas rooms are provided, such rooms shall be separated from other areas by not less than 1-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712, or both. [F]
415.7.3Floors in storage rooms. Floors in storage areas for corrosive liquids and highlytoxic or toxic materials shall be of liquid-tight, noncombustible construction. [F]
415.7.4Separation-highly toxic solids and liquids. Highlytoxic solids and liquids not stored in approved hazardous materials storage cabinets shall be isolated from other hazardous materials storage by not less than 1-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712, or both.[F]

780 CMR, 415.7