Current through Register Vol. 48, No. 10, October 25, 2024
Section 61-58.4.D - Distribution Systems(1) Materials Standards--Pipe, fittings, packing, jointing materials, valves and fire hydrants shall conform to Section C of the American Water Works Association (AWWA) Standards. All materials or products which come into contact with drinking water shall be certified as meeting the specifications of the American National Standard Institute/National Sanitation Foundation Standard 61, Drinking Water System Components--Health Effects. The certifying party shall be accredited by the American National Standards Institute. In the absence of American Water Works Association (AWWA) Standards, materials meeting applicable Product Standards and acceptable to the Department may be selected. SD 26 Class 160 and SD 21 Class 200 PVC pipe meeting ASTM Standard D1785 or D2241 are acceptable in sizes twelve (12) inches and smaller. Asbestos cement pipe shall not be used in potable water systems except in the repair of existing asbestos cement lines. Metallic pipe and fittings shall be lead free in accordance with R.61-58.4(F)(F). Thermoplastic pipe shall not be used above grade.(2) Used Materials--Water mains which have been used previously for conveying potable water may be reused provided they meet the above standards and have been thoroughly cleaned and restored practically to their original condition.(3) Gaskets and Joints--Gaskets, O-rings, and other products used for jointing pipes, setting meters or valves, or other appurtenances which will expose the material to the water shall comply with the requirements of R.61-58.4(D)(1)(D)(1) and shall not be made of natural rubber or any other material which will support microbiological growth. Lubricants which will support microbiological growth shall not be used for slip-on joints. The use of vegetable shortening to lubricate joints is prohibited. The use of solvent-weld PVC pipe and fittings in water mains four (4) inches and larger is prohibited.(4) Line Sizing-- (a) Pressure--The minimum pressure in all public water mains under conditions of maximum instantaneous demand shall be twenty-five (25) pounds per square inch at every customer's tap. Twenty (20) pounds per square inch will be acceptable at any tap when fire flows or flushing flows are provided in excess of maximum peak hourly flow.(b) Diameter--The minimum size of water main for providing fire protection and serving fire hydrants shall be six (6) inches in diameter. Larger size mains will be required if necessary to allow the withdrawal of the required fire flow while maintaining the minimum residual pressure specified in R.61-58.4(D)(4)(a)(D)(4)(a).(5) No line extension shall be made of an existing line when the existing line does not meet the minimum pressure and flow requirements of this regulation.(6) Dead ends-- (a) Dead ends shall be minimized by looping of all mains whenever practical.(b) The lengths of small dead end lines shall not exceed the following: (i) One (1) inch diameter--150 ft.(ii) One and one quarter (1 1/4) inch--200 ft.(iii) One and one half (1 1/2) inch--300 ft.(iv) Two inches (2)--1500 ft. Conditions may warrant having less than the above maximum lengths in order to meet the twenty-five (25) pounds per square inch pressure requirement.
(7) Flushing--The design shall provide for a readily accessible means of flushing all water lines at a minimum velocity of 2.5 feet per second. This does not apply to service lines. (a) Where dead-end lines occur they shall be provided with a fire hydrant if flow and pressure are sufficient, or with a post hydrant or readily accessible blow-off valve in a box for flushing purposes, except for the following cases: (i) Lines one and one half (1-1/2) inches in diameter and smaller will not require blow-offs. Two inch lines shorter than two hundred (200) feet will not require a blow-off. However, a service connection shall be installed at the end of the line or another acceptable means of bleeding chlorine through the lines must be provided.(b) Blow-offs shall be sized to provide a minimum velocity of 2.5 feet per second in the line and maintain a residual pressure of twenty-five (25) pounds per square inch.(c) Post-type hydrants are acceptable for flushing purposes on lines four (4) inch through eight (8) inch and can be used on three (3) inch lines where the design flow is increased to one hundred (100) gallons per minute in excess of peak hourly flow.(d) Design head loss calculations, including elevation changes shall show twenty-five (25) pounds per square inch minimum residual when instantaneous demand occurs or twenty (20) pounds per square inch minimum residual when either fire flow or flushing flow in excess of peak hourly flow occurs, whichever is greater.(e) Lines ten (10) inches and larger require flows in excess of five hundred (500) gallons per minute to achieve a two and a half (2.5) feet per second scouring velocity. This would require a standard fire hydrant or other approved blow-off, for flushing which must be designed to provide at least five hundred (500) gallons per minute in excess of peak hourly flow and a minimum residual pressure of twenty (20) pounds per square inch.(f) No flushing device shall be directly connected to any sewer.(8) Valves--Sufficient valves shall be provided on water mains so that customer inconvenience and sanitary hazards will be minimized during repairs.(9) Hydrants-- (a) Where Standard four (4) to six (6) inch diameter hydrants are proposed, the design flow shall not be less than five hundred (500) gallons per minute over and above peak hourly flow. Standard hydrants shall not be placed on systems using only hydropneumatic storage, unless standby power is provided and the pumping capacity from wells or ground storage exceeds the fire flow demand with the largest well or pump out of service. Standard hydrants shall not be connected to lines not designed to carry fire flows. (i) Hydrant Leads--The hydrant leads shall be a minimum of six (6) inches in diameter. Auxiliary gate valves shall be installed in all hydrant leads.(ii) Drainage--A gravel pocket or dry well shall be provided unless the natural soils will provide adequate drainage. Hydrant drains shall not be connected to or located within ten (10) feet of sanitary sewers.(b) Where Post-type hydrants are proposed, they must meet the flow requirements for blow-offs in R.61-58.4.D(7). Post hydrants shall not be used on lines smaller than three (3) inches. Design calculations must be submitted when utilizing post hydrants on three (3) inch lines. These calculations must show one hundred (100) gallons per minute in excess of peak hourly flow can be maintained, and provide a residual pressure greater than or equal to twenty (20) pounds per square inch.(10) Air Relief Valves, Valve, Meter and Blow-Off Chambers (a) Air relief valves--Air relief valves shall be provided in accordance with sound engineering practice at high points in water mains as required. Automatic air relief valves shall not be used in situations where flooding of the manhole or chamber may occur.(b) Air relief valve piping--The open end of an air relief pipe from automatic valves or from a manually operated valve shall be extended to the top of the pit and provided with a screened downward facing elbow.(c) Chamber drainage--Chambers, pits or manholes containing valves, blow-off, meters, air release valves, or other such appurtenances to a distribution system, shall not be connected directly to any storm drain or sanitary sewer.(11) Installation of Mains-- (a) Standards--Construction specifications shall incorporate the provisions of Section C of the American Waterworks Association (AWWA) Standards and/or manufacturer's recommended installation procedures.(b) Bedding--A continuous and uniform bedding shall be provided in the trench for all buried pipe. Back-fill material shall be tamped in layers around the pipe and to a sufficient height above the pipe to adequately support and protect the pipe. Stones, other than crushed bedding, shall not come in contact with the pipe and shall not be within six (6) inches of the pipe..(c) Cover--All water mains shall be provided with a minimum thirty (30) inches of cover. Where this is not possible, pipe shall be steel, concrete, ductile iron, or other approved material and method approved by the Department, and, when necessary, insulated to prevent freezing.(d) Blocking--All tees, bends, plugs and hydrants on lines two and one half inches in diameter and larger shall be provided with reaction blocking, tie rods or other approved restraining methods to prevent movement.(e) Pressure and leakage testing--All newly installed pipe shall be pressure tested and leakage tested in accordance with American Water Works Association (AWWA) Standard C600.(f) Disinfection--Disinfection of all new water mains shall be in accordance with current American Water Works Association (AWWA) Standard C651 for the disinfection of water mains. In general one approved method referred to as "continuous feed method" is as follows: Before being placed in service, all new mains shall be thoroughly flushed then chlorinated with not less than twenty-five (25) milligrams per liter of available chlorine. Water from the existing distribution system or other source of supply shall be controlled so as to flow slowly into the newly laid pipeline during the application of chlorine. The solution shall be retained in the pipeline for not less than twenty-four (24) hours and then flushed thoroughly with a potable water of satisfactory bacteriological quality before starting the sampling program. The contractor or owner shall collect a minimum of two (2) samples from each sampling site for total coliform analysis. The number of sites depends on the amount of new construction but must include all dead-end lines and be representative of the water in the newly constructed mains. Prior to sampling, the chlorine residual must be reduced to normal system residual levels or be non-detectable in those systems not chlorinating. These samples must be collected at least twenty-four (24) hours apart and must show the water line to be absent of total coliform bacteria. The chlorine residual must also be measured and reported. If the membrane filter method of analysis is used for the coliform analysis, non-coliform growth must also be reported. If the non-coliform growth is greater than eighty (80) colonies per one hundred (100) milliliters, the sample result is invalid and must be repeated. All samples must be analyzed by a certified laboratory. The Department may request that heterotrophic plate count analyses be conducted on a case-by-case basis where disinfection problems are suspected.
(g) Detection of mains--All mains shall be detectable within three (3) feet with electronic locating equipment. Non-metallic pipes shall be installed with copper wire or other means of detection.(h) Contaminated Areas - All water mains shall be located out of all contaminated areas. If the main must run through a contaminated site, the main material must protect the water system from being contaminated (e.g. Ductile Iron Pipe with chemical resistant gaskets).(12) Separation of Water Mains and Sewers-- (a) Parallel installation--Water mains shall be laid at least ten (10) feet horizontally from any existing or proposed sewer. The distance shall be measured edge to edge. In cases where it is not practical to maintain a ten foot separation, the Department may allow deviation on a case-by-case basis, if supported by data from the design engineer. Such deviation may allow installation of the water main closer to a sewer, provided that the water main is laid in a separate trench or on an undisturbed earth shelf located on one side of the sewer at such an elevation that the bottom of the water main is at least eighteen (18) inches above the top of the sewer.(b) Crossings--Water mains crossing sewers shall be laid to provide a minimum vertical separation of eighteen (18) inches between the outside of the water main and the outside of the sewer. This shall be the case whether the water main is either above or below the sewer line. Whenever possible, the water main shall be located above the sewer line. Where a new water main crosses a new sewer line, a full length of pipe shall be used for both the water main and sewer line and the crossing shall be arranged so that the joints of each line will be as far as possible from the point of crossing and each other. Where a new water main crosses an existing sewer line, one full length of water pipe shall be located so both joints will be as far from the sewer line as possible. Where a water main crosses under a sewer, adequate structural support shall be provided for the sewer line to prevent damage to the water main.(c) Special Conditions--When it is impossible to obtain the distances specified in R.61-58.4(D)(12)(a) and (b)(D)(12)(a) and (b) the Department may allow an alternative design. Any alternative design shall: (i) maximize the distances between the water main and sewer line and the joints of each;(ii) use materials which meet the requirements R.61-58.4(D)(1)(D)(1)for the sewer line; and,(iii) allow enough distance to make repairs to one of the lines without damaging the other.(d) Force mains--There shall be at least a ten (10) foot horizontal separation between water mains and sanitary sewer force mains. There shall be an eighteen (18) inch vertical separation at crossing as required in R.61-58.4(D)(12)(a) and (b)(D)(12)(a) and (b).(e) Sewer manholes--No water pipe shall pass through or come in contact with any part of a sewer manhole. Water lines may come in contact with storm sewers or catch basins if there is no other practical alternative, provided that ductile iron is used, no joints of the water line are within the storm sewer or catch basin and the joints are located as far as possible from the storm sewer or catch basin.(f) Drain-fields and Spray-fields--Potable water lines shall not be laid less than twenty-five (25) feet horizontally from any portion of a waste-water tile-field or spray-field, or shall be otherwise protected by an acceptable method approved by the Department.(13) Surface Water Crossings-- (a) Above-water crossings--The pipe shall be adequately supported and anchored, protected from damage and freezing, and accessible for repair or replacement.(b) Underwater crossings--A minimum cover of two (2) feet shall be provided over the pipe. When crossing water courses which are greater than fifteen (15) feet in width, the following shall be provided: (i) The pipe material and joints shall be designed appropriately;(ii) Valves shall be located so that the section can be isolated for testing or repair; the valves shall be easily accessible, and not subject to flooding; and,(iii) A blow-off shall be provided on the side opposite the supply service, sized in accordance with R.61-58.4(D)(7)(D)(7).(iv) Blow-offs shall not be directed toward creeks or other water bodies without proper precaution being taken to dechlorinate prior to discharge.(14) Cross Connections and Interconnections-- (a) Cross connections--There shall be no connection between the distribution system and any pipes, pumps, hydrants, or tanks whereby unsafe water or other contamination materials may be discharged or drawn into the system.(b) Cooling water--Neither steam condensate nor cooling water from engine jackets or other heat exchange devices shall be returned to the potable water supply.(c) Interconnections--The approval of the Department shall be obtained for interconnections between potable water supplies.(15) Water Services and Plumbing-- (a) Plumbing--Water services and plumbing shall conform to relevant local plumbing codes or to the National Plumbing Code.(b) Booster pumps--Individual home booster pumps shall not be allowed to meet the twenty-five (25) pounds per square inch minimum pressure at the service connection.(16) Water Loading Stations--To prevent contamination of the public supply, the following criteria shall be met: (a) Air Gap--A device shall be installed on the fill line to provide an air break and prevent a submerged discharge line.(b) Hose length--The fill hose and cross connection control device must be constructed so that when hanging freely it will terminate at least two (2) feet above the ground surface.(c) Fill line terminus--The discharge end of the fill line must be unthreaded and constructed to prevent the attachment of additional hose, piping or other appurtenances.S.C. Code Regs. § 61-58.4.D