Current through October 31, 2024
Section 153.351 - Location of 4m vent dischargesExcept as prescribed in § 153.353 , a 4m venting system must discharge:
(a) At least 4m (approx. 13.1 ft) above the higher of:(2) any walkway that is within a 4m (approx. 13.1 ft) horizontal radius from the vent discharge.(b) At least 10m (approx. 32.8 ft) from air intakes for, or openings into, accommodation or service spaces.CGD 78-128, 47 FR 21208, May 17, 1982