Cal. Code Regs. tit. 8 § 4826

Current through Register 2024 Notice Reg. No. 45, November 8, 2024
Section 4826 - Testing

Piping systems shall be tested and proved gas-tight at 1 1/2 times the maximum working pressure and shall be thoroughly purged of air before being placed in service. The material used for testing oxygen lines shall be oil-free and non-combustible, flames shall not be used to detect leaks.

Cal. Code Regs. Tit. 8, § 4826

1. Amendment filed 6-12-87; operative 7-12-87 (Register 87, No. 26).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

1. Amendment filed 6-12-87; operative 7-12-87 (Register 87, No. 26).