Cal. Code Regs. tit. 17 § 7602

Current through Register 2024 Notice Reg. No. 45, November 8, 2024
Section 7602 - Construction of Backflow Preventers
(a) Air-gap Separation. An Air-gap separation (AG) shall be at least double the diameter of the supply pipe, measured vertically from the flood rim of the receiving vessel to the supply pipe; however, in no case shall this separation be less than one inch.
(b) Double Check Valve Assembly. A required double check valve assembly (DC) shall, as a minimum, conform to the AWWA Standard C506-78 (R83) adopted on January 28, 1978 for Double Check Valve Type Backflow Preventive Devices which is herein incorporated by reference.
(c) Reduced Pressure Principle Backflow Prevention Device. A required reduced pressure principle backflow prevention device (RP) shall, as a minimum, conform to the AWWA Standard C506-78 (R83) adopted on January 28, 1978 for Reduced Pressure Principle Type Backflow Prevention Devices which is herein incorporated by reference.

Cal. Code Regs. Tit. 17, § 7602

1. New section filed 5-26-87; operative 6-25-87 (Register 87, No. 23).

Note: Authority cited: Sections 208 and 4026, Health and Safety Code. Reference: Section 4026, Health and Safety Code.

1. New section filed 5-26-87; operative 6-25-87 (Register 87, No. 23).