Section 51-11C-40243 - Section C402.5.5-Rooms containing fuel-burning appliances
C402.5.5Rooms containing fuel-burning appliances. Where combustion air is supplied through openings in an exterior wall to a room or space containing a space conditioning fuel-burning appliance, one of the following shall apply:
1. The room or space containing the appliance shall be located outside of the building thermal envelope.
2. The room or space containing the appliance shall be enclosed and isolated from conditioned spaces inside the building thermal envelope. Such rooms shall comply with all of the following:
2.1. The walls, floor and ceiling that separate the enclosed room or space from the conditioned spaces shall be insulated to be at least equivalent to the insulation requirement of below grade walls as specified in Table C402.1.3 or C402.1.4.
2.2. The walls, floors and ceilings that separate the enclosed room or space from conditioned spaces be sealed in accordance with Section C402.5.1.1.
2.3. The doors into the enclosed room or space shall be fully gasketed.
2.4. Water lines and ducts in the enclosed room or space shall be insulated in accordance with Section C403.
2.5. Where the air duct supplying combustion air to the enclosed room or space passes through conditioned space, the duct shall be insulated to an R-value of not less than R-16.

EXCEPTION:

Fireplaces and stoves complying with Sections 901 through 905 of the International Mechanical Code, and Section 2111.14 of the International Building Code.

Wash. Admin. Code § 51-11C-40243

Amended by WSR 16-03-072, Filed 1/19/2016, effective 7/1/2016
Amended by WSR 19-24-040, Filed 11/26/2019, effective 7/1/2020
Amended by WSR 22-14-091, Filed 7/1/2022, effective 7/1/2023
Amended by WSR 24-16-145, Filed 8/7/2024, effective 9/7/2024

Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. 13-04-056, § 51-11C-40243, filed 2/1/13, effective 7/1/13.